The tube is the detector, the nozzle and the switch
A pressurised polymer tube leaves the cylinder and makes six passes across the equipment faces, so every unit sits within a few centimetres of it. It bursts where it is hottest and the agent leaves through the same tube — no solenoid, no control panel, no wiring. Drag the model to look around it.
Cylinder charged, tube pressurised. The tube is the detector: no panel, no wiring, no power supply.
- 01Monitoring
- 02Overheating
- 03Tube bursts
- 04Direct discharge
- 05Fire out
- 06Secured
- DetectorPressurised tube, closed circuit
- Release pointAt the burst, in the rack
- AgentHFC-227ea / FK-5-1-1
- Electrical supplyNone required
The cylinder is mounted on the left-hand post of the rack; the tube runs up the side, passes through a grommet into the cabinet and then makes six passes across the equipment faces before the end fitting — the pattern used in the reference drawing. The burst sits a few centimetres above the equipment that is burning, so the discharge lands on it rather than in the cold air at the top of the rack. The tube is single-use and is replaced as a whole after every release.