Server rooms, telecom exchanges and control rooms are protected as a volume: agent calculated against the real room, detection cross-zoned so one dirty head cannot empty it, and a pre-discharge delay long enough for someone to look.
A data centre fire almost never starts as flame. It starts as a terminal screw, a capacitor or a cable bundle smouldering behind a rack — and by the time it is visible, the room is already full of the smoke that writes off the equipment.
CRAC units and in-row cooling dilute smoke and carry it away from ceiling detectors. The airflow that keeps the servers alive is also what delays the alarm.
Rack density keeps climbing. Every extra kilowatt adds terminals, connectors and joints that loosen under thermal cycling — and every one of them is a place a fire can start.
A sprinkler that saves the building still destroys what it lands on. The fire can be out and the room unusable for weeks afterwards.
Many rooms are unmanned at night and at weekends. Detection has to alarm, delay and discharge without waiting for someone to walk in and smell it.
Agent quantity is a function of net room volume, the lowest expected room temperature and the design concentration — not of the number of racks. We calculate against the drawing, then check that the enclosure can actually hold that concentration long enough to work.
The rack beside the room is not a second room system. It is a self-contained 2U unit inside one cabinet — no cylinder room, no pipework through the building, and no discharge the rest of the data centre ever notices.
The animation above shows the standalone rack beside the room: fourteen 1U rack-mounted servers on a 19-inch frame, three roof nozzles, and a 2U FK-5-1-1 module at the bottom. Here is what that module actually is.
Not every server room justifies a total-flooding system. Where the risk is concentrated — an edge site, a telecom cabinet, one rack of network gear in an office — a 2U FK-5-1-1 module goes into the bottom of the cabinet and protects that cabinet only.
The most expensive failure in a server room is not the fire. It is the discharge nobody needed — followed by a week of cleaning and a room full of replaced hardware.
The first detector in the zone goes into alarm. The panel drives a local sounder and, where the site has one, signals the building management system. No agent, no shutdown.
A second, different detector in the same zone has to confirm. Cross-zoning is what stops a dusty smoke head or a maintenance shortcut from emptying the room.
Sounders and beacons run, HVAC and fire dampers close, doors release. The delay is set long enough for staff to reach the abort switch or leave the room — and short enough that the fire does not grow past the design.
The solenoid opens, the agent reaches design concentration within the discharge time, and the room stays sealed until it is safe to ventilate. Re-entry is a measurement, not a guess.
The right one depends on room size, whether a cylinder store exists, and whether the risk is the whole room or one cabinet inside it.

A cylinder bank outside the room, a manifold and a nozzle grid on the ceiling. The standard answer for a purpose-built server hall or a telecom exchange.

A pre-engineered unit fixes inside the rack or cabinet it protects: agent, gas generator and nozzle in one slim body that stores nothing under pressure. No cylinder room, no pipework — one unit per enclosure, up to 3 m³.

Where the risk sits in a single wall cabinet or rack — a telecom cabinet in a corridor, a switchgear box on a factory floor — a sealed cylinder bolts inside the enclosure. The agent sits at zero pressure, so there is no pipework, no cylinder room and nothing to leak; the thermal cord runs to the hottest point and fires at 175 °C, with a 24 V release as the alternative.
A server room is rarely one compartment. The floor void, the ceiling void and the room itself each hold cable and each has to be counted as its own volume.
Cable trays and the cooling plenum. Nozzles are placed under the floor tiles with detection in the same void, because a fire in the plenum is invisible from the aisle.
Own volumeAbove a suspended ceiling is a second compartment, often full of data cable and often forgotten. It is flooded as its own volume, not left to the room design.
Separate calculationDucts and penetrations that leave the room are sealed, so the concentration holds under discharge and the fire cannot travel to the next compartment.
Enclosure integrityThe same sheet leaves us whether the project is a 60 m³ telecom room or a 1,800 m³ data hall.
| Design | GB 50370-2005 · NFPA 2001 · EN 15004-1 · ISO 14520 |
|---|---|
| Detection & alarm | GB 50116-2013 · cross-zoned, two-stage alarm with abort switch |
| Agent | HFC-227ea (FM-200) · FK-5-1-1 (Novec 1230) |
| Discharge | ≤10 s to design concentration · hold time ≥10 min |
| Enclosure | Pressure relief vent sized to the peak discharge rate; door-fan test where required |
| Documentation | Calculation sheet, P&ID, nozzle layout, O&M manual, as-built drawings |
| Lead time | 20–30 days for equipment, including filling and testing |
| Supply terms | ODM / OEM |
Nozzle layout, cylinder size and vent area are project deliverables, not catalogue values. Send the plan and section and we return a calculation you can put in front of a reviewer.
Everything else we can ask for once the first pass is done — but without these four the numbers would be a guess.
Room drawing with dimensions, plus the floor and ceiling void depths if the room has them.
Number of racks, approximate kW each, and whether the load is expected to grow.
What is installed today, which panel, and whether a BMS or DCIM has to be interfaced.
Lowest and highest room temperature, access route for cylinders, and who commissions.

You get the agent quantity, the nozzle plan and the equipment list — before any commercial discussion.